                        MO Minimum : Elevators
                     | 
                    
                        11 CSR 40-5.090 Inspection and Testing
                     | 
                    
                        (3) Testing Procedures (Re-Inspect)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Need to perform the following tests to complete the inspection: car safeties, emergency battery lowering, emergency light, stop ring pressure & low pressure switch. Re-inspection required
                     | 
                    
                        
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        (G) - Maintenance, Repair and Replacements
                     | 
                    
                        (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
                     | 
                    
                            x
                     | 
                    
                            x
                     | 
                    
                        Emergency phone in car does not work, has no alarm button. Red-tagged, Re-inspection required
                     | 
                    
                        
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        3.2 - Car top light and outlet
                     | 
                    
                        2.14.7
                     | 
                    
                     | 
                    
                     | 
                    
                        Light on top of car shall work
                     | 
                    
                        
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        11 CSR 40-5.090 Inspection and Testing
                     | 
                    
                        8.11 Periodic Inspection and Test.
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        This unit is a roped hydraulic LULA with an installation year of 2013. A category 5 test is required in 2020.
                     | 
                    
                        1/27/2021
                     |