Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 Yes No Perform the required tests on the Overspeed Valve 6/28/2023
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 Yes No OSV is due for testing, provide.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.37 - Pressure Switch 8.11.3.2.5 Pressure Switch (Re-Inspection) Yes No Repair inoperative low pressure switch 5/28/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 No No Increase the machine room lighting to 19ft candles minimum
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Lighting No No Provide machine room lighting (foot candles at the floor ) to be code compliant.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.8 - Hoistway enclosure 2.1.1 No No Water is entering the hoistway from the top. Repair as needed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No Provide current year tested fire extinguisher in the elevator machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1.1.1 Means of Communication (Red Tag) Yes Yes No operating phone or alarm Repair as needed 6/28/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.37 - Pressure Switch 8.11.3.2.5 Pressure Switch (Re-Inspection) Yes No Repair inoperative low pressure switch 6/28/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Lighting No No Provide at least 19 foot candles of illumination in the machine room
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No The pit shall be kept clean. Clean the pit.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.11.2.1.2(e) (Re-Inspection) No No The machine room shall be kept clean. Clean the machine room. 4/8/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. Yes No This is a roped hydraulic LU/LA. A category 1 test of the safeties shall be performed and witnessed. 4/8/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.3 - Top-of-car operating device 8.11.2.1.3(c) No No The car top inspection station does not operate as designed and would not operate properly. The device shall be repaired or replaced to operate as designed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) No No The machine room lighting was not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The testing has not been completed on the elevator at this time. The weight test shall be performed, safeties set, and buffers compressed before the inspection is completed. 6/7/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) Yes No Perform the required Cat 5 tests on the Overspeed Valve 5/28/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate.