Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.13 x OSV tested, failed. Repair as needed. 4/30/2024
A17.1-2016 : Elevators 2.37 - Pressure Switch 8.6.5.14.5 Repair inoperative low pressure switch
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Maintenance records shall be kept on-site. 8/28/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.12 - Car Buffer 8.11.3.1.5(d) Straighten the buffer support in the pit. 8/28/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 4/7/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces Observed black mold on the ceiling in the elevator machine room, abate as needed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.8 - Door closing force 2.13.4.2.3 x Door force exceeds code, adjust as needed. 4/30/2024
conversion conversion n/a Remove mold from ceiling in elevator machine room. 8/28/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Repair inoperative emergency phone
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x Testing of the OSV needs completed Failed to complete in 2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces Replace drywall ceiling section covered in black mold and reseal ceiling to maintain the machine room fire rating