Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Inside car light bulbs and fixtures need to be covered or protected from accidental breakage. 2/8/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 No No Door closing force exceeds 30 lbs 3/23/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)10 Car Floors Yes No Floor inside elevator needs to be replaced. 2/8/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Fire service key switch needs to be replaced. 2/8/2024
MO Minimum : Elevators (A) - Hoistways (A)13 Yes No Vent at top of the hoisway needs a fire damper. 4/3/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 Yes No Need to remove multiple phone line boxes in the machine room. 4/3/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 Yes No Drain pipe in the machine room must be guttered or guarded to prevent leakage onto elevator equipment. 4/3/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test Yes No Still need to test Phase I and Phase II fire service recall and need to test smoke and heat detector recall. 4/3/2025