A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.11.3.1.5(a)
|
|
|
Remove oil from pit floor 2.2.2.3
|
12/21/2022
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.11.3.1.5(a)
|
|
|
Empty Drip pans in the pit 2.2.2.3
|
12/21/2022
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Battery lowering unit not working maximum 30 days
|
12/19/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.36 - Hydraulic Cylinders
|
3.18.3
|
x
|
|
Jack seal leaking, needs to be replaced.
|
12/9/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Clean pit of dirt and oil.
|
3/19/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
Door close button shall work on car fire service recall. Did NOT red tag the elevator.
|
12/9/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
clean jack dip pans in pit
|
1/8/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
Provide monthly fire service test & document on log posted in machine room
|
1/8/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
REpair phone in car
|
1/7/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean drip pans in pit
|
2/17/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Perform monthly fire service test and document on log in machine room 1206.3
|
12/21/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Remove oil from pit floor. Written up on last inspection and still not completed 30 day maximum
|
12/18/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
Empty drip pans in pit was written up last inspection and still not completed 30 day maximum
|
12/18/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergemcy comminication/phone not working maximum 30 days
|
12/19/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Empty drip pans and oil oil from pit floor
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
Seal and tag overspeed valve which was tested 11/15/23
|
|