Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Battery lowering unit not working maximum 30 days 12/19/2023
MO Minimum : Elevators (I) - Pits (I)1 Clean drip pans in pit 2/17/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits clean jack dip pans in pit 1/8/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean pit of dirt and oil. 3/19/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x Door close button shall work on car fire service recall. Did NOT red tag the elevator. 12/9/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergemcy comminication/phone not working maximum 30 days 12/19/2023
MO Minimum : Elevators (I) - Pits (I)1 Empty drip pans and oil oil from pit floor
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance Empty drip pans in pit was written up last inspection and still not completed 30 day maximum 12/18/2023
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.3.1.5(a) Empty Drip pans in the pit 2.2.2.3 12/21/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.36 - Hydraulic Cylinders 3.18.3 x Jack seal leaking, needs to be replaced. 12/9/2019
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service test and document on log in machine room 1206.3 12/21/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing Provide monthly fire service test & document on log posted in machine room 1/8/2020
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.3.1.5(a) Remove oil from pit floor 2.2.2.3 12/21/2022
MO Minimum : Elevators (I) - Pits (I)1 Remove oil from pit floor. Written up on last inspection and still not completed 30 day maximum 12/18/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x REpair phone in car 1/7/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Seal and tag overspeed valve which was tested 11/15/23