MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Light guards, diffusers & bulbs missing from inside of elevator
|
3/23/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Platen plate shall be re-fastened to bolster channels and worn isolation pads replaced
|
3/23/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
The fire extinguisher is expired. A current tested and tagged ABC type fire extinguisher shall be provided in the machine room.
|
2/8/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.6 Verification of Telephone Operability
|
x
|
|
Emergency communications monitor shall work.
|
12/18/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
A gutter system shall be installed under air conditioning unit over top of unit number 2 to divert water away from pump unit.
|
12/18/2024
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
All phases of fire service shall work. All smoke detectors shall be inspected.
|
12/18/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
A gutter system shall be installed under air conditioning unit over top of unit number 2 to divert water away from pump unit. The drain pan is on-site but has not been installed yet.
|
3/21/2025
|