A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Up-to-date operating certificate required in the machine room.
|
|
A17.1-1996 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
102.1
|
|
|
Water pipe above the hydraulic tank shall be guarded or guttered to divert any potential leaks away from tank.
|
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1206.2b (Clean Machine Room)
|
|
|
Machine room shall not be used for storage. There is also a sink in the machine room. Remove the sink or separate equipment per code. Customer may need to apply for a variance.
|
|
conversion
|
conversion
|
n/a
|
|
|
Clean Drip Pan (remove oil) in machine room
|
8/31/2018
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site.
|
7/8/2021
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed.
|
7/8/2021
|
A17.1-1996 : Elevators
|
1.16 - Rated load, platform area, and data plate
|
1001.2(a)(16)
|
|
|
A capacity plate shall be provided in the car.
|
7/8/2021
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
The means to restrict opening of the car door shall be operational.
|
8/11/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
11/19/2024
|