ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency power needs to be tested. Re-inspection required
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone in elevator cab does not work. line problem. Re-inspection required
|
4/10/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The elevator ADA telephone inside the elevator is not operating correctly. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required in 14 days.
|
4/5/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The testing has not been completed on the elevator at this time. The weight test shall be performed, safeties set, and buffers compressed before the inspection is completed.
|
4/5/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Elevator appears to have emergency generator backup power operation, which needs to be tested to complete inspection. Re-inspection required
|
4/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
2.7.5.2
|
|
|
The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
2.7.5.2
|
|
|
The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
2.7.5.2
|
|
|
The HVAS unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
2.7.5.2
|
|
|
The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
2.7.5.2
|
|
|
The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.7 - Car leveling and anticreep devices
|
8.11.2.1.3(j)
|
|
|
Readjust load-weighing to prevent rollback.
|
11/17/2020
|