A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required.
|
6/8/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.8 - Door closing force
|
8.11.2.1.1(h)
|
x
|
|
The rear door closing force exceeds 30 lb. limit and shall be adjusted.
|
4/15/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
Perform the required Overspeed Valve tests
|
2/15/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
|
|
The pit lighting shall be operational.
|
11/12/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.14 - Supply Piping
|
8.11.3.1.5(i)
|
|
|
Rupture valve is not sealed. A category 5 test shall be conducted on the rupture valve during the 2021 annual inspection.
|
11/12/2020
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
3.19.4.7.5(a)
|
x
|
|
OSV testing failed, repair or replace as needed.
|
3/8/2024
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
x
|
|
Need to preform the required Cat 5 tests on OSV. Re-inspection required
|
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
|
|
This elevator has an overspeed valve device installed that is not sealed and is now required to have a 5 year full load test performed. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection is required.
|
|
conversion
|
conversion
|
n/a
|
|
|
Machine room shall not be used for storage of non-elevator related materials.
|
9/25/2019
|
conversion
|
conversion
|
n/a
|
|
|
Machine room fire extinguisher is expired.
|
9/25/2019
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
|