Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Machine room fire extinguisher is expired. 9/25/2019
conversion conversion n/a Machine room shall not be used for storage of non-elevator related materials. 9/25/2019
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 x Need to preform the required Cat 5 tests on OSV. Re-inspection required
A17.1-2016 : Elevators 5.15 - Overspeed Valve 3.19.4.7.5(a) x OSV testing failed, repair or replace as needed. 3/8/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x Perform the required Overspeed Valve tests 2/15/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.14 - Supply Piping 8.11.3.1.5(i) Rupture valve is not sealed. A category 5 test shall be conducted on the rupture valve during the 2021 annual inspection. 11/12/2020
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required. 6/8/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits The pit lighting shall be operational. 11/12/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.8 - Door closing force 8.11.2.1.1(h) x The rear door closing force exceeds 30 lb. limit and shall be adjusted. 4/15/2022
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 This elevator has an overspeed valve device installed that is not sealed and is now required to have a 5 year full load test performed. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection is required.