ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 1/6/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.8 - Door closing force 8.11.2.1.1(h) x The door closing force exceeds the 30 lbs. limit. 2/25/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an overspeed valve that in not sealed. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test.