A17.1-1996 : Elevators
|
2.4 - Machine space
|
101.1a
|
|
|
machine room ceiling sheetrock has been removed after water damage and collapse, replace ceiling for fire resistive construction
|
7/12/2024
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
|
|
The machine room light fixture is hanging by the power cord up against the wall since the entire ceiling collapsed
|
4/12/2024
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5c Receptacles
|
|
|
when the ceiling collapsed the 110 outlet was broken and needs to be replaced
|
7/12/2024
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the state operating certificate in the machine room expired in 2017, update with the current copy when received from the state
|
5/6/2022
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
need to have a monthly fire service test log kept in the machine room
|
5/6/2022
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.5.7 Record of Oil Usage
|
|
|
need to have a maintenance control program book in the machine room to include oil record log
|
5/6/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
the emergency phone did not work because the cell phone control box in the machine room was plugged into the outlet that was broken during the ceiling collapse
|
2/23/2024
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
pit light did not work, may be a bad bulb or the breaker is off
|
|
A17.1-1996 : Elevators
|
4.8 - Hoistway enclosure
|
100.1
|
|
|
repair large hole in the sheetrock wall of the elevator pit
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
need to post a new copy of the state operating certificate in the machine room every year, the certificate in the machine room is from 2017
|
7/12/2024
|
conversion
|
conversion
|
n/a
|
|
|
Replace burnt out car top light bulb
|
7/12/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
need to have a Maintenance Control Program (MCP) kept in the machine room
|
7/12/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
need a monthly fire service test log kept in the machine room
|
7/12/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone has a dial tone, dials a number, then gets busy signal. phone is to dial a number that is answered 24 hours a day 7 days a week.
|
5/6/2022
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
water in the tank in the machine room. water got into the hydraulic oil when the ceiling collapsed, replace the hydraulic oil
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.11.1 Firefighters' Emergency Operation & Documentation
|
|
|
A monthly fire service test shall be completed and a log kept in the machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
Need to have a maintenance control program in the machine room
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Machine room light not working, replace burnt out light bulb
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Heat detector is not mounted within 18 inches of the sprinkler head and the smoke detector is not mounted to the ceiling it is just hanging by the wiring
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Operating certificate in the machine room expired in 2017, update with the current copy of the state operating certificate when received from the state
|
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
Water in the hydraulic oil, hydraulic oil needs to be replaced
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light is not working, repair pit light
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Patch Huge hole in the sheetrock wall at pit level
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency phone is Not working, provide working phone line to the elevator machine room
|
|