Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Replace burnt out car top light bulb 7/12/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate need to post a new copy of the state operating certificate in the machine room every year, the certificate in the machine room is from 2017 7/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records need to have a Maintenance Control Program (MCP) kept in the machine room 7/12/2024
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log need a monthly fire service test log kept in the machine room 7/12/2024
A17.1-1996 : Elevators 2.4 - Machine space 101.1a machine room ceiling sheetrock has been removed after water damage and collapse, replace ceiling for fire resistive construction 7/12/2024
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting The machine room light fixture is hanging by the power cord up against the wall since the entire ceiling collapsed 4/12/2024
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5c Receptacles when the ceiling collapsed the 110 outlet was broken and needs to be replaced 7/12/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate the state operating certificate in the machine room expired in 2017, update with the current copy when received from the state 5/6/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 need to have a monthly fire service test log kept in the machine room 5/6/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.5.7 Record of Oil Usage need to have a maintenance control program book in the machine room to include oil record log 5/6/2022
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits pit light did not work, may be a bad bulb or the breaker is off
A17.1-1996 : Elevators 4.8 - Hoistway enclosure 100.1 repair large hole in the sheetrock wall of the elevator pit
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 water in the tank in the machine room. water got into the hydraulic oil when the ceiling collapsed, replace the hydraulic oil
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation A monthly fire service test shall be completed and a log kept in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Need to have a maintenance control program in the machine room
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room light not working, replace burnt out light bulb
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Operating certificate in the machine room expired in 2017, update with the current copy of the state operating certificate when received from the state
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 Water in the hydraulic oil, hydraulic oil needs to be replaced
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light is not working, repair pit light
MO Minimum : Elevators (A) - Hoistways (A)13 Patch Huge hole in the sheetrock wall at pit level
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency phone is Not working, provide working phone line to the elevator machine room
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Heat detector is not mounted within 18 inches of the sprinkler head and the smoke detector is not mounted to the ceiling it is just hanging by the wiring
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x the emergency phone did not work because the cell phone control box in the machine room was plugged into the outlet that was broken during the ceiling collapse 2/23/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x emergency phone has a dial tone, dials a number, then gets busy signal. phone is to dial a number that is answered 24 hours a day 7 days a week. 5/6/2022