MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
repair broken hinge on controller access door in top landing jamb
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
8.11.2.3.2
|
x
|
|
repair/replace governor remote trip solenoid, it didn't work
|
10/16/2019
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
the onsite documentation is not to be stored in the hoistway
|
1/20/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.11.1
|
|
|
Perform monthly fire service test and post test log in the machine room
|
1/20/2021
|
A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.6.3.2 (Re-Inspection)
|
x
|
|
the coated steel belt monitor is flashing an error, reset the monitor or replace the belts if they are failing (8.6.3.2.3)
|
10/31/2023
|
A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.11.2.1.3(cc)
|
x
|
|
coated steel belt monitor is flashing an error, verify that the belts are still good and reset/repair the belt monitor
|
11/17/2022
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.7 Firefighters’ Emergency Operation: Operating Procedures (Signage)
|
|
|
the fire service phase 1 instruction sign is missing
|
1/20/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
since the elevator does not have a machine room, display the state operating certificate on the top landing next to the elevator entrance
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the operating certificate should be updated annually
|
1/20/2021
|