Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate since the elevator does not have a machine room, display the state operating certificate on the top landing next to the elevator entrance
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts repair broken hinge on controller access door in top landing jamb
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 8.11.2.3.2 x repair/replace governor remote trip solenoid, it didn't work 10/16/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.11.1 Perform monthly fire service test and post test log in the machine room 1/20/2021
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) the onsite documentation is not to be stored in the hoistway 1/20/2021
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate the operating certificate should be updated annually 1/20/2021
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters’ Emergency Operation: Operating Procedures (Signage) the fire service phase 1 instruction sign is missing 1/20/2021
A17.1-2016 : Elevators 3.23 - Suspension Means 8.11.2.1.3(cc) x coated steel belt monitor is flashing an error, verify that the belts are still good and reset/repair the belt monitor 11/17/2022
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.3.2 (Re-Inspection) x the coated steel belt monitor is flashing an error, reset the monitor or replace the belts if they are failing (8.6.3.2.3) 10/31/2023