Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) the onsite documentation is to be stored in a location outside the hoistway readily accessible to elevator personnel, not on the car top 1/20/2021
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate the state operating certificate is to be updated annually 1/20/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 8.11.2.3.2 x repair/replace governor remote trip soilenoid, it didn't work 10/16/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.11.1 Perform monthly fire service test and post test log in the machine room 1/20/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x Emergency light battery is dead, replace battery 1/22/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Repair the emergency lights.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate since this elevator does not have a machine room, display the operating certificate on the top landing next to the elevator entrance