Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements G(1). EBR (Emergency Brake Release) unplugged. Shall be repaired/replaced, (REINSPECTION REQUIRED) 10/14/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self-closing and self-locking. Does not close completely to latch. 3/8/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 2.7.5.1 : Machinery Space lighting (top of hoistway) not working. 3/8/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) 620-85 Nec reccepticle needs to be a GFCI in machine room 9/12/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) air conditioner needs repaired in machine room 9/12/2018
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly. (Provided by Elevator Serv Co.) 3/8/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Emergency communications loss monitor shall work. 3/8/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x emergency light is on all the time 8/27/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x telephone will not call out 8/27/2021
conversion conversion n/a control wiring diagrams need to be on job site 9/12/2018