Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x Only one emergency light bulb is working, check and make sure bulbs are in all the way, drop ceiling bolted together couldn’t reach fixture to check bulbs 1/20/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability the communication failure device did not work, repair device
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.11.1 Perform monthly fire service test and post test log in the machine room 1/20/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.28 - Counterweight and counterweight buffer 8.11.2.1.3(m) replace missing counterweight slide guide insert 1/20/2021
A17.1-2016 : Elevators 4.8 - Hoistway enclosure 8.11.2.1.4(h) sheetrock screws projecting into the hoistway need to be cut off flush with the wall
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate the state operating certificate on display in the machine room expired in 2019, update annually with the current certificate when received from the state
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate the sate operating certificate is to be updated annually 1/20/2021