Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
Missouri Minimum : Platform Lifts | (U) - Existing Vertical and Inclined Platform Lifts | 10.1.5 Installation Placed Out of Service | x | x | Reference A17.1 Part XX 1984 Ed Rule 2000.1a(2)(3) Unit operating with electrical locks not working. Rule 2000.9(b) Lower terminal stopping device not working. Rule 2000.1 Key operation at all stations not working. Rule 2000.10f Emergency Stop switch on platform not working. Red Tagged Unit | 2/24/2023 |