Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 A Packing on right side piston is leaking oil. Identify and correct the cause of excessive oil leakage. 1/10/2023
conversion conversion conversion - reinspect x Alarm Bell shall work 3/14/2019
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. There are oil soaked pads and oil on the pit floor.
MO Minimum : Elevators (H) - Machine Rooms (H)4 Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in machinery spaces, machine rooms, control spaces, and control rooms. Remove used oil and used oil drying compound. 1/10/2023
conversion conversion n/a Both Hydraulic cylinder need repacking 5/27/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean pit to remove debris, water and/or oil and address sources. Oil dry is all over pit 7/1/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 3.18 Cylinders are leaking oil. Packing needs to be replaced. REINSPECTION REQUIRED. 5/27/2020
conversion conversion n/a Elevator Pit needs to be clean and dry 5/27/2020
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 Oil collection containers shall not be allowed to overflow.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - n/a n/a Remove oil from pit. 5/27/2020
MO Minimum : Elevators (I) - Pits (I)1 Remove oil/oily pads on the pit floor and sump hole. All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. 1/1/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x The audible buzzer, which activates when the elevator initiates fire fighter's operation, is not functioning.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts The plastic border around the COP is broken off creating an opening around the COP. The electrical wiring is exposed.
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 Where pressure piping, valves, and cylinders use packing glands or seals, they shall be examined and maintained to prevent excessive loss of fluid.