Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No The plastic border around the COP is broken off creating an opening around the COP. The electrical wiring is exposed. 4/23/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Remove oil/oily pads pads on the pit floor and sump hole. All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. 1/1/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Equipped with emergency backup generator. Elevator shall be tested for emergency power operation. 12/19/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Alarm bell not working. 3/2/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency light does not work. 3/30/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Oil Accumulation on Pit floor 3/16/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. Oil has accumlated on the pit floor. 4/23/2026