MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
:Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil loss log and Fire service testing log, recorded monthly
|
5/9/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
1.18/8.6.4.13.1(l): Car Door restrictor shall work.
|
3/31/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
1/5/21: Car Door restrictor shall work {front and rear}. (REINSPECTION REQUIRED)
|
8/11/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.11 Runby (Re-Inspection)
|
x
|
|
1/5/21; Insufficient Counterweight runby. Shorten or replace suspension cables.
|
8/11/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
2-way communication device shall work and give proper location
|
3/31/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
2-way communication device shall work and give proper location
|
3/31/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
G(1)/A17.1-2016:8.6.1.2.1(a)/2.40 Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly. (Provided by Elev Co.)
|
3/8/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Mount/repair dangling board in Controller.
|
5/9/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
Provide MCP in machine room
|
2/5/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Repair loose Car Handrails
|
5/9/2022
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Replace missing box cover on Cab Fan
|
5/9/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Replace missing fire service phase 1 instructions on Main landing.
|
5/9/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
Restrictor shall work. 30day reinspection
|
5/9/2022
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1202.14
|
x
|
|
suspension ropes need to be shortened
|
3/30/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
TESTING INCOMPLETE. MUST RETURN TO COMPLETE.
|
3/31/2022
|