ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
2.4.2
|
x
|
|
2.4.3 - Provide counterweight runby sign in pit.
|
8/3/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
3/16/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.11.2.1.2(e) (Re-Inspection)
|
|
|
Clean the car top.
|
8/3/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
Clean the pit.
|
3/16/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.1.4(l)
|
x
|
x
|
Emergency fire service shall be tested.
|
6/5/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
x
|
|
Emergency power & Fire service still need to be tested. This was also not tested in 2023 and needs to be completed ASAP.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
x
|
|
Emergency power operation and fire service operation shall be tested.
|
7/9/2024
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Emergency rescue device does not work.
|
5/29/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
8.11.2.1.2(o)
|
x
|
|
Emergency rescue device does not work. (Violation not cleared from previous annual inspection)
|
8/3/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.40 - Maintenance Records
|
2.26.1.4 Inspection Operation
|
|
|
Provide MCP.
|
3/16/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.11.2.1.5(b)
|
x
|
x
|
Provide proper runby clearance.
|
8/3/2020
|
conversion
|
conversion
|
n/a
|
|
|
The top of the pit ladder needs to be securely fastened.
|
3/16/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
The top of the pit ladder needs to be securely fastened. (Violation not cleared from previous annual inspection)
|
3/16/2022
|