Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)1 The space between the solid cab wall of the elevator to the top of the elevator shall be enclosed with a non-combustible solid material or non-combustible lattice work with holes that will reject a ball 1.5 inches in diameter. 9/18/2018
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x In car alarm bell shall work. 6/23/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x x The in car emergency alarm and emergency lighting shall be operational. - Unit Red Tagged for inoperative emergency services. 4/22/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Lobby & 3rd floor hall call shall work. 7/22/2021
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The machine room lighting shall be operational. 7/22/2021
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The pit lighting shall be operational. 7/22/2021
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and dry. 7/22/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting In car light switch shall be fixed. 7/22/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Only the relief valve pressure test was able to be performed. Could not get unit running. The rest of the category 1 annual inspection shall be completed. 9/3/2021
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)6 Each freight enclosure shall have a capacity plate. loading class plates, and a "No Passengers" sign conspicuously posted. Letters shall not be less than one half inch (1/2") high. 9/24/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods 1st floor rear door and 2nd floor both doors have non-wire glass in the vision panels and shall be replaced. 9/24/2021
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)5 The cab lights shall be guarded. 9/24/2021
MO Minimum : Elevators (A) - Hoistways (A)10 Means to access the hoistway shall be in a locked box. 9/24/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods A seam in the cab wall is damaged and requires repair. 9/24/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The hoistway door chains are not properly attached on 1st floor rear door and both doors on the 3rd floor. Take corrective action. 9/24/2021
MO Minimum : Elevators (A) - Hoistways (A)5 Hoistway door pull straps are required on the inside and outside of all doors. 9/24/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 9/24/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods RECOMMENDATIONS - NOT VIOLATIONS: It is strongly recommended that the hoistway doors should have the rigid astragals replaced with non-shearing astragals. It is also recommended to paint the bottom hoistway door panel floor stops and the area underneath the door stops a contrasting color. 9/24/2021
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)6 x Each freight enclosure shall have a capacity plate. loading class plates, and a "No Passengers" sign conspicuously posted. Letters shall not be less than one half inch (1/2") high. (2nd Notice - Re-Inspection Required) 6/16/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements x 110.7 - 1st floor rear door and 2nd floor both doors have non-wire glass in the vision panels and shall be replaced. (2nd Notice - Re-Inspection Required) 6/16/2023
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)5 x The cab lights shall be guarded. (2nd Notice - Re-Inspection Required) 6/16/2023
MO Minimum : Elevators (A) - Hoistways (A)10 x Means to access the hoistway shall be in a locked box. (2nd Notice - Re-Inspection Required) 6/16/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts x A seam in the cab wall is damaged and requires repair. (2nd Notice - Re-Inspection Required) 6/16/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts x The hoistway door chains are not properly attached on 1st floor rear door and both doors on the 3rd floor. Take corrective action. (2nd Notice - Re-Inspection Required) 6/16/2023
MO Minimum : Elevators (A) - Hoistways (A)5 x Hoistway door pull straps are required on the inside and outside of all doors. (2nd Notice - Re-Inspection Required) 6/16/2023