MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
x
|
|
110.7 - 1st floor rear door and 2nd floor both doors have non-wire glass in the vision panels and shall be replaced. (2nd Notice - Re-Inspection Required)
|
6/16/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
1st floor rear door and 2nd floor both doors have non-wire glass in the vision panels and shall be replaced.
|
9/24/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
9/24/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
A seam in the cab wall is damaged and requires repair.
|
9/24/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
x
|
|
A seam in the cab wall is damaged and requires repair. (2nd Notice - Re-Inspection Required)
|
6/16/2023
|
MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)6
|
|
|
Each freight enclosure shall have a capacity plate. loading class plates, and a "No Passengers" sign conspicuously posted. Letters shall not be less than one half inch (1/2") high.
|
9/24/2021
|
MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)6
|
x
|
|
Each freight enclosure shall have a capacity plate. loading class plates, and a "No Passengers" sign conspicuously posted. Letters shall not be less than one half inch (1/2") high. (2nd Notice - Re-Inspection Required)
|
6/16/2023
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)5
|
|
|
Hoistway door pull straps are required on the inside and outside of all doors.
|
9/24/2021
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)5
|
x
|
|
Hoistway door pull straps are required on the inside and outside of all doors. (2nd Notice - Re-Inspection Required)
|
6/16/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
In car alarm bell shall work.
|
6/23/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
In car light switch shall be fixed.
|
7/22/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Lobby & 3rd floor hall call shall work.
|
7/22/2021
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)10
|
|
|
Means to access the hoistway shall be in a locked box.
|
9/24/2021
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)10
|
x
|
|
Means to access the hoistway shall be in a locked box. (2nd Notice - Re-Inspection Required)
|
6/16/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Only the relief valve pressure test was able to be performed. Could not get unit running. The rest of the category 1 annual inspection shall be completed.
|
9/3/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
RECOMMENDATIONS - NOT VIOLATIONS: It is strongly recommended that the hoistway doors should have the rigid astragals replaced with non-shearing astragals. It is also recommended to paint the bottom hoistway door panel floor stops and the area underneath the door stops a contrasting color.
|
9/24/2021
|
MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)5
|
|
|
The cab lights shall be guarded.
|
9/24/2021
|
MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)5
|
x
|
|
The cab lights shall be guarded. (2nd Notice - Re-Inspection Required)
|
6/16/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
The hoistway door chains are not properly attached on 1st floor rear door and both doors on the 3rd floor. Take corrective action.
|
9/24/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
x
|
|
The hoistway door chains are not properly attached on 1st floor rear door and both doors on the 3rd floor. Take corrective action. (2nd Notice - Re-Inspection Required)
|
6/16/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
x
|
The in car emergency alarm and emergency lighting shall be operational. - Unit Red Tagged for inoperative emergency services.
|
4/22/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
The machine room lighting shall be operational.
|
7/22/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
The pit lighting shall be operational.
|
7/22/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit shall be kept clean and dry.
|
7/22/2021
|
MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)1
|
|
|
The space between the solid cab wall of the elevator to the top of the elevator shall be enclosed with a non-combustible solid material or non-combustible lattice work with holes that will reject a ball 1.5 inches in diameter.
|
9/18/2018
|