MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
H(8). 4x4 electrical box (Phone wiring) in machine room needs to have wiring inside box and cover installed.
|
3/31/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)6
|
|
|
H(6). Machinery, controllers, governors, disconnects shall be numbered conspicuously.
|
3/31/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
Provide MCP in machine room
|
5/3/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
remove rubbish and material from machine room floor
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Replace the hoist ropes due to undersizing
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
1/5/21:: 2-way communication device shall work and give proper location (REINSPECTION REQUIRED)
|
8/11/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
2-way communication device shall work and give proper location (REINSPECTION REQUIRED)
|
8/11/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
TESTING INCOMPLETE. MUST RETURN TO COMPLETE. Required within 30days
|
3/16/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
TESTING INCOMPLETE. MUST RETURN TO COMPLETE. Required within 30days
|
3/16/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
B(11)/1.6.1/ : 2-way communication device shall work and give proper location (REINSPECTION 14days to REDTAG)
|
3/31/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
TESTING INCOMPLETE. Fire Service and Door# be tested to complete. F.S. Keys needed
|
3/31/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
B(11)/1.6.1/ : 2-way communication device shall work and give proper location (REINSPECTION 14days to REDTAG)
|
3/31/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
TESTING INCOMPLETE. Fire Service and Door# be tested to complete. F.S. Keys needed
|
3/31/2022
|