MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The category 5 full load testing shall be completed. The only item of the category 5 test that was able to be completed was the relief pressure with a full load. All other category 5 testing items remain.
|
3/1/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
There were issues getting the unit to operate properly. All annual inspection items still need to be tested with the exception of the relief pressure.
|
3/1/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The low pressure switch does not work and shall be operational.
|
8/29/2022
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)1
|
|
|
The hoistway door sill grout on the outside of the "G" landing shall be repaired.
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)3
|
|
|
Adjust the "G" level hoistway door to close properly.
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
The illumination inside the car enclosure shall be operational. Note: One of the two lighting fixtures inside the car aren't working.
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Car enclosure lights shall be operational.
|
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)6
|
x
|
|
Reverse phase relay has been removed and a jumper has been installed in its place. Replace proper device.
|
8/29/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The in car emergency telephone shall be operational.
|
8/29/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency light shall be operational.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The machine room door shall be self-closing and self-locking.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
There is an excessive amount of oil on the pit floor. The pit shall be kept clean and dry.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
The pit lighting shall be operational.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
The pit light shall be operational.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Firefighters phase one instructions shall be posted near the phase one key-switch in the hallway at the egress floor.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Firefighters phase two instructions shall be posted inside the car on the car operating panel.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Provide Phase 1 & 2 fire fighters instructions.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted near the equipment, in a noncombustible frame with a clear protective vision plate over it.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. Note: Display certificate is expired.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
The fire service phase one key-switch bezel shall be legible.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
A means shall be provided to collect the overflow oil from the jack head.
|
|