Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. Note: Display certificate is expired. 9/4/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted near the equipment, in a noncombustible frame with a clear protective vision plate over it. 9/4/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No A means shall be provided to collect the overflow oil from the jack head. 9/4/2025
MO Minimum : Elevators (A) - Hoistways (A)3 No No Adjust the "G" level hoistway door to close properly. 9/4/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Car enclosure lights shall be operational. 9/4/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency light shall be operational. 8/27/2025
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Firefighters phase one instructions shall be posted near the phase one key-switch in the hallway at the egress floor. 9/4/2025
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Firefighters phase two instructions shall be posted inside the car on the car operating panel. 9/4/2025
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Provide Phase 1 & 2 fire fighters instructions. 9/4/2025
MO Minimum : Elevators (F) - Electrical Switches (F)6 Yes No Reverse phase relay has been removed and a jumper has been installed in its place. Replace proper device. 8/29/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The category 5 full load testing shall be completed. The only item of the category 5 test that was able to be completed was the relief pressure with a full load. All other category 5 testing items remain. 3/1/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No The fire service phase one key-switch bezel shall be legible. 9/4/2025
MO Minimum : Elevators (A) - Hoistways (A)1 No No The hoistway door sill grout on the outside of the "G" landing shall be repaired. 9/4/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No The illumination inside the car enclosure shall be operational. Note: One of the two lighting fixtures inside the car aren't working. 9/4/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No The in car emergency telephone shall be operational. 8/29/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The low pressure switch does not work and shall be operational. 8/29/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No The machine room door shall be self-closing and self-locking. 9/4/2025
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No The pit light shall be operational. 9/4/2025
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No The pit lighting shall be operational. 9/4/2025
MO Minimum : Elevators (I) - Pits (I)1 No No There is an excessive amount of oil on the pit floor. The pit shall be kept clean and dry. 9/4/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No There were issues getting the unit to operate properly. All annual inspection items still need to be tested with the exception of the relief pressure. 3/1/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 9/4/2025