Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an overspeed valve. Based on the installation date of 2013, a category 5 test is due on or before the next annual inspection.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(b)(1) 1) A record that shall include the maintenance tasks listed with the associated requirements of Section 8.6 identified in the Maintenance Control Program. Ref: 8.6.1.4.1(a)(1) 3/5/2021