MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
When main power is removed Emergency Light does not work on backup power
|
7/25/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.17 - Door and gate equipment
|
8.11.2.1.3(w)
|
|
|
Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail.
|
7/27/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6
|
7/27/2022
|
A17.1-2016 : Elevators
|
3.17 - Door and gate equipment
|
8.6.4.13
|
|
|
Bottom safety retainers missing from hoistway doors. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail.
|
5/17/2024
|