MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.7.2 Periodic Test Record (Test Tags)
|
|
|
Install 5 year test tag
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
MRL not up to date
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.4.11
|
x
|
|
Need to shorten hoist ropes. Countweight buffer is fully compressed before top final limit actuates.
|
4/30/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
No current state operating certificate on site.
|
11/15/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone does not operate.
|
11/9/2018
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(b)
|
|
|
Provide written documentation of how to perform tests, and periodic inspections for installed equipment. Documentation to be kept inside the elevator control space.
|
11/15/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
state operating certificate not displayed
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed in control space
|
|
A17.1-2016 : Elevators
|
2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection
|
8.6.4.19.11 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake
|
x
|
|
Test ascending car protection.
|
11/29/2023
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(b)(5)
|
|
|
Written documentation of procedures to perform tests and periodic inspections need to be kept on site.
|
|