Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit Clean up the mess in the pit. 9/21/2021
MO Minimum : Elevators (I) - Pits (I)1 Remove the standing water and oil from the pit floor, 7/19/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Replace the worn door gibb. 7/19/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Clean the dirty car top. 7/19/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Re fire seal around the doors at each level inside the hoistway 7/19/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Emergency light and bell not working 9/5/2018
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Repair the pit light it is burnt out 10/15/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Repair the emergency alarm bell as it will not ring 11/15/2019
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 x Relocate the main disconnect to provide the NEC required 3'6" clearance in front of the disconnect from the floor to the structure fix date 4/30/24above. 4/16/2024