Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) x Must make emegency light operable. 8.6.4.15 3/17/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Must make Emegency phone operable. ( currently no live phone line) 8.6.4.15 1/30/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Must make Emergency Alarm operable. 8.6.4.15 3/17/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Must Make Emergency Phone Operable. 8.6.4.15 2/20/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits Must make Pit light operable. 8/12/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Must make two way communication devise operable.1.6 6/20/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.3 - Operating control devices 8.11.2.1.1(c) Must mount Phase I fire service key switch and Hoistway Access Key switch in Hall Station face plate. Currently both are not secured & held in by wires) 8/12/2022
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Must post Current State operating Cert. in Mach. Room. 5.100(2) 2/20/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Must post current State operating Cert. in Machine room. 8/12/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) Must provide and Maintain MCP Documents and Logs. 8.6.1.4 8/12/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Must provide current Test tag on machine room fire Extinguisher. 2.7 8/12/2022