Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 2.26.12 Yes No Replace the missing braille plates at several floors. 5/22/2026
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Provide a working emergency phone. 5/22/2026
A17.1-2016 : Elevators 10.15 - Response to smoke detectors 8.6.8.15.17 Yes No Raise the smoke detector in the hoistway up to within 12 inches of the hoistway ceiling. 5/22/2026
A17.1-2016 : Elevators 10.15 - Response to smoke detectors 8.6.8.15.17 Yes No Provide additional conductors and contact to send a signal from the hoistway and machine room to the controller to liglht up the fire hat. 5/22/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit No No clean the dirty pit 7/19/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Clean the dirty car top 7/19/2023