A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Provide a working emergency phone.
|
5/22/2026
|
|
A17.1-2016 : Elevators
|
1.15 - sign and operating device symbols
|
2.26.12
|
Yes
|
No
|
Replace the missing braille plates at several floors.
|
5/22/2026
|
|
A17.1-2016 : Elevators
|
10.15 - Response to smoke detectors
|
8.6.8.15.17
|
Yes
|
No
|
Raise the smoke detector in the hoistway up to within 12 inches of the hoistway ceiling.
|
5/22/2026
|
|
A17.1-2016 : Elevators
|
10.15 - Response to smoke detectors
|
8.6.8.15.17
|
Yes
|
No
|
Provide additional conductors and contact to send a signal from the hoistway and machine room to the controller to liglht up the fire hat.
|
5/22/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.7 Cleaning of Hoistway and Pit
|
No
|
No
|
clean the dirty pit
|
7/19/2023
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
No
|
No
|
Clean the dirty car top
|