Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No The top floor elevator lobby is considered a machine space and needs to have a fire extinguisher within 10ft of the elevator
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No The emergency personnel answering the emergency phone were not able to determine the location of the elevator.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1.1.1 Means of Communication (Red Tag) No No Telephone in car doesn't work. Phone line dead to elevator 2/14/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency Light does not work when normal power is removed 3/28/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No For Machine roomless elevators, provide a fire extinguisher at the top floor near the elevator door 1/12/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) No No Fire Extinguisher located at top landing by the controller is expired 1/12/2026