MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Annual test was performed, failed because no Cat 5 test has been completed. Re-inspection required
|
7/29/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.14 - Ventilation
|
2.14.2.3
|
|
|
1.14.1: Cab forced ventilation fan shall work or remove fan and associated keyswitching.
|
10/12/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
11 CSR 40-5.100(2) : Current State Operating Permit shall be displayed in the Equipment Room
|
10/12/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
|
|
2.7.1: Machine Room Fire Extinguisher shall be installed
|
10/12/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
2.41 : MCP shall be kept in equipment room, including Testing Procedure and Fire service testing log, recorded monthly.
|
10/12/2020
|