MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
VIO2. TESTING INCOMPLETE. Fire Service and Door# be tested to complete. F.S. Keys needed
|
3/31/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
VIO2. TESTING INCOMPLETE. Fire Service and Door# be tested to complete. F.S. Keys needed
|
3/31/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
VIO1. B(11)/1.6.1/ : 2-way communication device shall work and give proper location (REINSPECTION 14days to REDTAG
|
3/31/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
VIO1. B(11)/1.6.1/ : 2-way communication device shall work and give proper location (REINSPECTION 14days to REDTAG
|
3/31/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
VIO3. G(1)1.18.1/8.6.4.13.1(l): Car Door restrictor shall work. (Front)
|
3/31/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
VIO3. G(1)1.18.1/8.6.4.13.1(l): Car Door restrictor shall work. (Front)
|
3/31/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
2.17 machine noisey--determine cause & repair or replace parts
|
1/30/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
VIO6. G(1). Replace non-functional lamp in Emergency Light fixture (1 of 2 lamps not working)
|
3/31/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean pit
|
5/3/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
|
|
VIO5. I(5). : Pit Ladder shall be installed , accessible from each Pit access opening for each elevator. (#217 has a ladder but not accessible from #218 pit)
|
5/3/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
|
|
Provide pit ladder #217 has one but not accessible from #218
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Car hoist ropes undersized, replace per code
|
8/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.18 - Traction drive machines
|
8.11.2.1.2(p)
|
x
|
|
1/5/21: Machine very noisy. Determine cause and repair/replace needed parts. REINSPECTION REQUIRED
|
8/11/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.18 - Traction drive machines
|
8.11.2.1.2(p)
|
x
|
|
Machine very noisy. Determine cause and repair/replace needed parts. REINSPECTION REQUIRED
|
8/11/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
Provide MCP in machine room
|
5/3/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
VIO4. G(1) Car-top light not working, clean cartop,clean pit
|
5/3/2022
|