ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency/auxiliary lighting shall work with power loss.
|
1/28/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV testing incomplete, Must return to complete
|
1/28/2022
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)2(D)
|
|
|
Relief valve shall be sealed.
|
2/4/2021
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)2(D)
|
|
|
Relief valve shall be sealed.
|
2/4/2021
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)2(B)
|
|
|
Relief valve shall be set greater than max no-load but lower than 125% of no-load
|
2/4/2021
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)2(B)
|
|
|
Relief valve shall be set greater than max no-load but lower than 125% of no-load
|
2/4/2021
|