MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A written copy of the MCP shall be kept in the machine room for each unit
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test incomplete, need to perform the following tests to complete inspection: perform relief valve pressure test of hydraulic system and test slack rope car safety with no load in the car. Re-inspection required
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
Emergency light fixture inside the elevator is not working, needs repaired. Re-inspection required
|
10/31/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.37 - Pressure Switch
|
8.11.3.2.5 Pressure Switch (Re-Inspection)
|
x
|
|
Replace defective low pressure switch
|
6/30/2025
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.37 - Pressure Switch
|
8.11.3.2.5 Pressure Switch (Re-Inspection)
|
x
|
|
Replace defective low pressure switch. Re-inspection required
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
Emergency light in elevator cab does not work, needs repaired. Re-inspection required
|
|