A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
3.19.4.7.5(a)
|
x
|
|
OSV testing failed.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Rooms and Machinery Spaces
|
|
|
Abate black mold.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Rooms and Machinery Spaces
|
|
|
Abate black mold from the entire hoistway.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.10 - Numbering of elevators, machines, and disconnect switches
|
2.29.1
|
|
|
Provide car position indicator and floor tactile/braille plates match.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
2/17/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6
|
x
|
|
Car station fire service lock is broken and shall be replaced.
|
2/17/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
8.11.2.1.3(p)
|
|
|
There are holes and openings in the hoistway from the ceiling to the second floor. The hoist way shall be fully enclosed.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
1/11/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
3.26.10 (Auxiliary Power)(Re-Inspection)
|
x
|
|
Battery lowering device does not work per code. Where auxiliary power lowering operation is installed or altered, it shall conform to 3.26.10.
|
1/11/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.2 - Stop switches
|
8.11.2.1.1(b) (Re-Inspection)
|
x
|
|
In Phase 1, could not test the stop key switch in flight.
|
1/11/2023
|
conversion
|
conversion
|
n/a
|
|
|
Provide numbering of units, car top, pits, and machine room.
|
9/15/2020
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
In cab emergency telephone shall work and have 24/7 support.
|
9/15/2020
|
conversion
|
conversion
|
n/a
|
|
|
Remove all mold from hoistway.
|
9/15/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning)
|
|
|
Evacuation procedures need to be included in the MCP
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone in car is not working. Re-inspection required
|
2/22/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher is expired, replace or have serviced.
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Repair all holes in hoistway walls, including drywall tape falling off entire length of hoistway
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide existing phone to work.
|
2/22/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide existing phone to work.
|
|