Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Provide correct floor numbering. (Does not match with other unit down the hall)
conversion conversion n/a Provide numbering of units, car top, pits, and machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 8.11.2.1.3(p) There are openings in the hoistway at the ceiling. The hoist way shall be fully enclosed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 Repair hole in hoistway wall at 2nd floor and openings at hoistway ceiling. Hoistway shall be fully enclosed
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Fire extinguisher in machine room is expired, replace or have serviced.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Maintenance control program shall include evacuation procedures
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.37 - Pressure Switch 3.26.8 Pressure Switch Pressure switch failed testing, repair/replace as needed.
A17.1-2016 : Elevators 5.15 - Overspeed Valve 3.19.4.7.5(a) x OSV testing failed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone in car is not working. Re-inspection required 2/22/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Provide existing phone to work. 2/22/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Provide existing phone to work.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 1/11/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.2 - Stop switches 8.11.2.1.1(b) (Re-Inspection) x In Phase 1, could not test the stop key switch in flight. 1/11/2023
conversion conversion conversion - reinspect x Provide a cab emergency phone that works and has 24/7 support. 9/15/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x x The in car emergency phone shall be operational. Elevator Red Tagged for Phone and Alarm bell both not working. 9/16/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x x The alarm buzzer does not work. Elevator Red Tagged for Phone and Alarm bell both not working. 9/16/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency phone shall be operational. 2/17/2022