Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.8 - Door closing force 8.11.2.1.1(h) x The front and rear door closing force exceeds the 30 lbs. limit. 1/6/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Perform the required Cat 5 testing on the Overspeed Valve
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.1 Examination and Maintenance of Packing Glands and Seals x Repair the hydraulic oil leak. 1/6/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.3 - Top-of-car operating device 8.11.2.1.3(c) The car top inspection station does not operate as designed and would not operate properly. The device shall be repaired or replaced to operate as designed.