MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)8
|
|
|
governor did not trip at the correct speed. it is supposed to trip at 175 fpm, we could not get it to trip before 250fpm. adjust, repair, or replace the governor. reinspection needed when governor is fixed.
|
4/6/2021
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Sweep machine room - fly infestation
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Install fire extinguisher near strike side of the door to the machine room
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
Provide maintenance control program and task logs
|
|