Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)8 governor did not trip at the correct speed. it is supposed to trip at 175 fpm, we could not get it to trip before 250fpm. adjust, repair, or replace the governor. reinspection needed when governor is fixed. 4/6/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Install fire extinguisher near strike side of the door to the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Provide maintenance control program and task logs
MO Minimum : Elevators (H) - Machine Rooms (H)4 Sweep machine room - fly infestation