A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
|
|
Provide testing of the OSV in the pit.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.19 - Car Ride
|
3.23
|
|
|
Car was unable to run at contract speeds in the down direction, repair as needed.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.8 - Door closing force
|
8.11.2.1.1(h)
|
x
|
|
The door closing force exceeds the 30 lbs limit.
|
1/8/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.2 - Car top light and outlet
|
8.11.2.1.3(b)
|
|
|
Provide a guard on the car top lamp.
|
1/26/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Provide current year tested fire extinguisher in the elevator machine room.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide existing phone to work, no power.
|
|