A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams)
|
|
|
Wiring diagrams can not be stored on top of elevator.
|
9/29/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(b)(1)
|
|
|
Provide written documentation on unique testing procedures, such as ascending car protection and unintended motion, and keep permanently on site.
|
12/23/2021
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(b)(1)
|
|
|
Written specific procedures for testing (i.e., ascending car protection , and unintended movement) need to be kept on site.
|
3/15/2023
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4 Instructions for Locating Maintenance Records
|
|
|
Instructions for obtaining maintenance records need to be listed on the controller, or at the means necessary for test.
|
3/15/2023
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
No written maintenance records on site for 2022
|
3/15/2023
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(c)(3)
|
|
|
Install periodic test tag for annual test in 2022, and 5 yeat test performed Jan 2020
|
3/15/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
Emergency light does not illuminate
|
3/15/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
2.14.1.7 Railing and Equipment on Top of Cars
|
|
|
Install top of car handrail where distance from hoistway wall to the edge of the car top enclosure exceeds 12 inches
|
3/15/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.7 Firefighters' Emergency Operation: Operating Procedures
|
|
|
Post firefighter operating instructions next to hall fire keyswitch
|
3/22/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.7 Firefighters' Emergency Operation: Operating Procedures
|
|
|
Remove Phase 2 firefighter instructions next to hall fire keyswitch. Post Phase 1 firefighter instructions next to hall fire keyswitch.
|
9/29/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
Test and log firefighter operation monthly
|
9/29/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Repair top of car blocking device. The blocking device does not engage with the rail mounted holding bracket
|
12/20/2023
|