A17.1-2016 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
2.20.9.5 Wedge Rope Sockets
|
|
|
2.20.9.4 - Hoist rope tail retaining clips shall be properly spaced.
|
7/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.28 - Counterweight and counterweight buffer
|
2.21
|
|
|
Counterweight hold down clamps need to be set properly.
|
7/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
2.24.8.4 Means for Manual Release
|
x
|
|
2.24.8.4 - EBR module failed to operate.
|
7/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6 Fire Fighters Operation (Re-Inspection)
|
x
|
|
Fire service testing incomplete. Unit faulted out of service. Fire service shall be tested.
|
7/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
11/10/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Compliant/required documentation and MCP shall be kept in equipment room including wiring diagrams, fire service log, etc.
|
1/4/2024
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Left side counter weight derailment wire does not activate seismic feature.
|
7/2/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Remove excess weight from car top.
|
7/2/2018
|