Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.9.5 Wedge Rope Sockets 2.20.9.4 - Hoist rope tail retaining clips shall be properly spaced. 7/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 2.24.8.4 Means for Manual Release x 2.24.8.4 - EBR module failed to operate. 7/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 11/10/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Compliant/required documentation and MCP shall be kept in equipment room including wiring diagrams, fire service log, etc. 1/4/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.28 - Counterweight and counterweight buffer 2.21 Counterweight hold down clamps need to be set properly. 7/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) x Fire service testing incomplete. Unit faulted out of service. Fire service shall be tested. 7/5/2024
conversion conversion conversion - reinspect x Left side counter weight derailment wire does not activate seismic feature. 7/2/2018
conversion conversion conversion - reinspect x Remove excess weight from car top. 7/2/2018